Skip to product information
VERTIV EMERSON 211NGFB Power Distribution Panel w/M830B Control Unit & R48-5000

VERTIV EMERSON 211NGFB Power Distribution Panel w/M830B Control Unit & R48-500

$1,020.00

Condition: Used

Condition Description: From a working unit, see pictures for more details

Brand: Emerson

Type: Power Distribution Panel

Model: 211NGFB & M830B & R48500

MPN: 211NGFB, R48-500, M830B

Unit Quantity: 1

Country of Origin: Mexico

VERTIV EMERSON 211NGFB Power Distribution Panel 
w/M830B Control Unit 
& 2x R48-500


Electrical Specifications
  • Nominal Output Voltage. -48 VDC (operational rectifier adjustment range from -42 VDC to -58 VDC).
  • Nominal AC Input. 120 / 208 / 240 VAC, single-phase, 3-wire (50/60 Hz nominal; 45 to 65 Hz acceptable range).
  • AC Operating Window. 100 VAC to 250 VAC system operating range (individual rectifiers support 85 VAC to 300 VAC with derating below 176 VAC).
  • Rectifier Modules. Compatible with hot-swappable R48-500 (500 W / 10.5 A at -48 VDC, 91% peak efficiency) and R48-1000 (1000 W / 20.9 A at -48 VDC, 92% peak efficiency) modules.
  • DC Distribution. Supports 1 A to 100 A bullet-nose circuit breakers (electrical/mechanical or electrical trip) and 0.18 A to 15 A GMT fuses.
  • Disconnect Options. Configurable with optional Low Voltage Battery Disconnect (LVBD) or Low Voltage Load Disconnect (LVLD) contactors.

Shelf Size Rack Width Max Rectifiers Max Power (1000W Modules) Max Current (@ -48 VDC)
1RU (1.75") 19" 2 modules 2,000 W 40 A
1RU (1.75") 23" 3 modules 3,000 W 60 A
2RU (3.50") 19" 4 modules 4,000 W 80 A
2RU (3.50") 23" 6 modules 6,000 W 120 A
Physical, Control & Environmental
  • Mounting Depth & Access. Approximately 12" to 12.4" (under 300 mm) depth for shallow enclosures, featuring full front access for installation and maintenance.
  • Controller & Communications. Uses the NCU (or legacy SCU+) controller with Ethernet, Web UI, SNMP v2/v3, Modbus, and RS232 interfaces, plus programmable alarm relays and ECO energy-saving mode.
  • Operating Temperature. -40 °C to +75 °C (-40 °F to +167 °F), with rectifier output derating above +65 °C (delivering 600 W at +65 °C).
  • Humidity & Cooling. 0% to 95% non-condensing humidity with front-to-rear variable-speed fan cooling.